Multiplier reference only. Confirm heater nameplate voltage, phase, steps, and controls.

Reference table

Use amps-per-kW multipliers for duct heater current estimates by voltage and phase.

Formula basis uses single-phase and balanced three-phase power equations for resistive heaters.
Voltage and phaseAmps per kWFormulaExample
120 V 1-phase8.331000 / 1205 kW x 8.33 = 41.7 A
208 V 1-phase4.811000 / 2085 kW x 4.81 = 24.0 A
240 V 1-phase4.171000 / 2405 kW x 4.17 = 20.8 A
600 V 3-phase0.961000 / (sqrt(3) x 600)30 kW x 0.96 = 28.9 A
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.