Formula variables
- Running kW is the expected steady load for each row.
- Running PF converts each row from kW to kVA.
- Starting kVA is the entered motor or equipment starting requirement.
- Generator PF converts recommended kVA to a kW context value.
Assumptions
- Running kVA is calculated from each load kW and running power factor.
- Starting kVA screen uses the largest entered starting load while other loads remain at running kVA.
- Margin is applied to both running and starting kVA before the larger requirement is selected.
- Generator manufacturer sizing, transient response, voltage dip, fuel type, altitude, temperature, and standby-system rules are outside this screen.
Examples
600 V generator screen. A 39 kW load set with one 75 kVA starting load screens to about 116.51 kVA required after 15 percent margin, so the next standard value is 125 kVA.
Starting-load workflow. Use the largest realistic starting scenario first, then confirm voltage dip and transient response with generator manufacturer tools.