Reference boundary

Full-load current arithmetic only. It does not set overcurrent protection or conductor protection.

Reference table

Convert common three-phase transformer kVA ratings to full-load current at 600 V.

Formula basis: three-phase full-load amps = kVA x 1000 / (sqrt(3) x line voltage).
Transformer kVA600 V 3-phase A480 V 3-phase AUse
1514.418Approximate line current at rated kVA
3028.936.1Approximate line current at rated kVA
4543.354.1Approximate line current at rated kVA
7572.290.2Approximate line current at rated kVA
112.5108.3135.3Approximate line current at rated kVA
150144.3180.4Approximate line current at rated kVA
225216.5270.6Approximate line current at rated kVA
300288.7360.8Approximate line current at rated kVA
500481.1601.4Approximate line current at rated kVA
750721.7902.1Approximate line current at rated kVA
1000962.31202.8Approximate line current at rated kVA
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.