Formula variables
- ID is raceway inside diameter in millimetres.
- OD is conductor outside diameter in millimetres.
- Count is the number of conductors in each group.
- Target fill percent is selected by the user for preliminary review.
Assumptions
- Use actual raceway inside diameter and conductor outside diameter from product data or the project reference table.
- The selected fill target is a planning input for review, not an installation approval.
- This calculator does not check conductor ampacity, derating, pulling tension, bend radius, conduit body fill, support spacing, product markings, or local authority requirements.
- Confirm the current Canadian Electrical Code, provincial or territorial requirements, utility rules, manufacturer instructions, and AHJ direction before using results for work.
Examples
Mixed conductor group. Three conductors at 6 mm OD plus one conductor at 9 mm OD in a 27 mm inside-diameter raceway estimates about 25.9 percent fill.
Product-data workflow. If a raceway type or conductor insulation has a different actual diameter, use the manufacturer value instead of a nominal trade-size label.