Generator kW/kVA/Amps Table incl. 600V
Generator kW/kVA/Amps Table incl. 600V reference with assumptions and boundary notes.
Reference boundary
Formula estimate only. Generator manufacturer data, transient response, and motor starting are separate checks.
Reference table
Estimate generator apparent power and three-phase 600 V current from kW and power factor.
| Generator kW | kVA at PF 0.80 | 600 V 3-phase A | Use |
|---|---|---|---|
| 10 | 12.5 | 12 | Steady-state apparent-power estimate |
| 20 | 25 | 24.1 | Steady-state apparent-power estimate |
| 30 | 37.5 | 36.1 | Steady-state apparent-power estimate |
| 50 | 62.5 | 60.1 | Steady-state apparent-power estimate |
| 75 | 93.8 | 90.2 | Steady-state apparent-power estimate |
| 100 | 125 | 120.3 | Steady-state apparent-power estimate |
| 150 | 187.5 | 180.4 | Steady-state apparent-power estimate |
| 250 | 312.5 | 300.7 | Steady-state apparent-power estimate |
| 500 | 625 | 601.4 | Steady-state apparent-power estimate |
| 1000 | 1250 | 1202.8 | Steady-state apparent-power estimate |
Use notes
- Use this table for preliminary reference and arithmetic checks only.
- Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.