Reference boundary

Transformer secondary fault-current estimate only. It does not determine equipment AIC/SCCR, utility contribution, motor contribution, or protective-device adequacy.

Reference table

Estimate transformer secondary fault current from full-load current and transformer impedance percent.

Formula basis: approximate secondary current = transformer full-load current / (impedance percent / 100).
Transformer kVASecondary VImpedance (%)Full-load AApprox. current (A)Boundary
45600543.3866transformer-only approximation; utility source impedance and motor contribution are not included
75600572.21443transformer-only approximation; utility source impedance and motor contribution are not included
1506005144.32887transformer-only approximation; utility source impedance and motor contribution are not included
3006005.75288.75020transformer-only approximation; utility source impedance and motor contribution are not included
5006005.75481.18367transformer-only approximation; utility source impedance and motor contribution are not included
752085208.24164transformer-only approximation; utility source impedance and motor contribution are not included
1502085416.48327transformer-only approximation; utility source impedance and motor contribution are not included
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.