Reference boundary

Expansion-joint planning reference only. Manufacturer instructions, joint travel, conduit type, supports, and field temperature govern actual settings.

Reference table

Estimate PVC expansion-joint travel and midpoint setting references from run length and temperature change examples.

Reference basis uses the same PVC thermal movement arithmetic with midpoint travel examples; manufacturer joint setting instructions govern field use.
Run length (m)Temperature change (C)Estimated movement (mm)Midpoint setting (mm)Boundary
102010.45.2joint travel and field setting come from the manufacturer instructions and measured installation temperature
104020.810.4joint travel and field setting come from the manufacturer instructions and measured installation temperature
302031.215.6joint travel and field setting come from the manufacturer instructions and measured installation temperature
304062.431.2joint travel and field setting come from the manufacturer instructions and measured installation temperature
504010452joint travel and field setting come from the manufacturer instructions and measured installation temperature
506015678joint travel and field setting come from the manufacturer instructions and measured installation temperature
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.