12V/24V DC Wire Run Length by Voltage Drop
12V/24V DC Wire Run Length by Voltage Drop reference with assumptions and boundary notes.
Reference boundary
Voltage-drop estimate only. It does not choose conductor ampacity, protection, battery fuse size, or product rating.
Reference table
Estimate one-way DC run length at a 3 percent voltage drop for selected copper conductors and currents.
| DC circuit | Current (A) | Copper size | Approx. one-way length (m) |
|---|---|---|---|
| 12 V DC | 10 | 14 AWG | 2.2 |
| 12 V DC | 10 | 12 AWG | 3.5 |
| 12 V DC | 10 | 10 AWG | 5.5 |
| 12 V DC | 10 | 8 AWG | 8.7 |
| 12 V DC | 20 | 14 AWG | 1.1 |
| 12 V DC | 20 | 12 AWG | 1.7 |
| 12 V DC | 20 | 10 AWG | 2.7 |
| 12 V DC | 20 | 8 AWG | 4.4 |
| 24 V DC | 10 | 14 AWG | 4.3 |
| 24 V DC | 10 | 12 AWG | 6.9 |
| 24 V DC | 10 | 10 AWG | 11 |
| 24 V DC | 10 | 8 AWG | 17.5 |
| 24 V DC | 20 | 14 AWG | 2.2 |
| 24 V DC | 20 | 12 AWG | 3.5 |
| 24 V DC | 20 | 10 AWG | 5.5 |
| 24 V DC | 20 | 8 AWG | 8.7 |
| 48 V DC | 20 | 14 AWG | 4.3 |
| 48 V DC | 20 | 12 AWG | 6.9 |
| 48 V DC | 20 | 10 AWG | 11 |
| 48 V DC | 20 | 8 AWG | 17.5 |
Use notes
- Use this table for preliminary reference and arithmetic checks only.
- Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.