Reference boundary

Apparent-power conversion only. It does not choose equipment or conductor ratings.

Reference table

Convert kVA to current for single-phase and three-phase Canadian voltage references.

Formula basis: single-phase amps = kVA x 1000 / volts; three-phase amps = kVA x 1000 / (sqrt(3) x volts).
kVA240 V 1-phase A208 V 3-phase A600 V 3-phase A
14.22.81
312.58.32.9
520.813.94.8
1041.727.89.6
1562.541.614.4
25104.269.424.1
37.5156.3104.136.1
45187.5124.943.3
75312.5208.272.2
112.5468.8312.3108.3
150625416.4144.3
3001250832.7288.7
5002083.31387.9481.1
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.