Reference boundary

Starting kVA estimate only. Generator alternator data, voltage-dip tolerance, starter method, motor load, and manufacturer sizing tools govern selection.

Reference table

Estimate generator starting kVA from motor horsepower and locked-rotor code-letter midpoint.

Reference basis uses code-letter midpoint kVA-per-hp planning bands; the actual motor nameplate and generator model data govern field use.
Motor hpCode letterkVA/hp midpointStarting kVABoundary
5F4.7524starting kVA estimate only; generator voltage-dip and motor-starting method require manufacturer review
10G5.353starting kVA estimate only; generator voltage-dip and motor-starting method require manufacturer review
25H6.3158starting kVA estimate only; generator voltage-dip and motor-starting method require manufacturer review
50J7.5375starting kVA estimate only; generator voltage-dip and motor-starting method require manufacturer review
75K8.5638starting kVA estimate only; generator voltage-dip and motor-starting method require manufacturer review
100L9.5950starting kVA estimate only; generator voltage-dip and motor-starting method require manufacturer review
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.