Reference boundary

Stake-spacing arithmetic only. Soil conditions, electrode geometry, buried utilities, instrument instructions, and qualified judgment govern the test setup.

Reference table

Reference simple probe placement arithmetic for fall-of-potential ground testing setup planning.

Formula basis: potential probe positions are percentages of current-probe distance for preliminary fall-of-potential setup planning.
Current probe distance (m)Potential probe at 50% (m)Potential probe at 61.8% (m)Potential probe at 70% (m)Boundary
201012.414Probe spacing is a setup reference, not a pass/fail target
301518.521Probe spacing is a setup reference, not a pass/fail target
502530.935Probe spacing is a setup reference, not a pass/fail target
1005061.870Probe spacing is a setup reference, not a pass/fail target
1507592.7105Probe spacing is a setup reference, not a pass/fail target
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.