Reference boundary

Preliminary run-length arithmetic only. The 3 percent threshold is a selected planning input, not a code limit or conductor approval.

Reference table

Estimate one-way copper conductor run length for selected currents at a 3 percent voltage-drop planning threshold.

Formula basis: one-way metres = allowed voltage drop x area / (circuit multiplier x resistivity x current).
Conductor sizeArea (mm2)120 V 1-phase, 20 A (m)240 V 1-phase, 40 A (m)600 V 3-phase, 100 A (m)Basis
14 AWG2.0810.910.912.5copper, 20 C resistivity, 3 percent drop
12 AWG3.3117.317.320copper, 20 C resistivity, 3 percent drop
10 AWG5.2627.527.531.7copper, 20 C resistivity, 3 percent drop
8 AWG8.3743.743.750.5copper, 20 C resistivity, 3 percent drop
6 AWG13.369.469.480.2copper, 20 C resistivity, 3 percent drop
4 AWG21.2110.7110.7127.8copper, 20 C resistivity, 3 percent drop
3 AWG26.7139.4139.4160.9copper, 20 C resistivity, 3 percent drop
2 AWG33.6175.4175.4202.5copper, 20 C resistivity, 3 percent drop
1 AWG42.4221.3221.3255.6copper, 20 C resistivity, 3 percent drop
1/0 AWG53.5279.3279.3322.5copper, 20 C resistivity, 3 percent drop
2/0 AWG67.4351.8351.8406.3copper, 20 C resistivity, 3 percent drop
3/0 AWG85443.7443.7512.4copper, 20 C resistivity, 3 percent drop
4/0 AWG107.2559.6559.6646.2copper, 20 C resistivity, 3 percent drop
250 kcmil126.7661.4661.4763.7copper, 20 C resistivity, 3 percent drop
350 kcmil177.3925.5925.51068.7copper, 20 C resistivity, 3 percent drop
500 kcmil253.41322.81322.81527.4copper, 20 C resistivity, 3 percent drop
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.