Reference boundary

Resistance comparison only. This table does not provide ampacity equivalence, conductor substitution, terminal compatibility, or installation approval.

Reference table

Compare copper conductor areas with the minimum aluminum area needed for equal or lower resistance at 20 C.

Formula basis: aluminum area for equal resistance = copper area x aluminum resistivity / copper resistivity, using 20 C material constants.
Copper sizeCopper area (mm2)Required aluminum area (mm2)Minimum aluminum sizeAluminum area (mm2)Boundary
14 AWG2.083.4110 AWG5.26Resistance-only comparison; not an ampacity or termination substitution
12 AWG3.315.438 AWG8.37Resistance-only comparison; not an ampacity or termination substitution
10 AWG5.268.626 AWG13.3Resistance-only comparison; not an ampacity or termination substitution
8 AWG8.3713.724 AWG21.2Resistance-only comparison; not an ampacity or termination substitution
6 AWG13.321.83 AWG26.7Resistance-only comparison; not an ampacity or termination substitution
4 AWG21.234.751 AWG42.4Resistance-only comparison; not an ampacity or termination substitution
3 AWG26.743.771/0 AWG53.5Resistance-only comparison; not an ampacity or termination substitution
2 AWG33.655.082/0 AWG67.4Resistance-only comparison; not an ampacity or termination substitution
1 AWG42.469.513/0 AWG85Resistance-only comparison; not an ampacity or termination substitution
1/0 AWG53.587.714/0 AWG107.2Resistance-only comparison; not an ampacity or termination substitution
2/0 AWG67.4110.49250 kcmil126.7Resistance-only comparison; not an ampacity or termination substitution
3/0 AWG85139.34300 kcmil152Resistance-only comparison; not an ampacity or termination substitution
4/0 AWG107.2175.74350 kcmil177.3Resistance-only comparison; not an ampacity or termination substitution
250 kcmil126.7207.71500 kcmil253.4Resistance-only comparison; not an ampacity or termination substitution
350 kcmil177.3290.66600 kcmil304Resistance-only comparison; not an ampacity or termination substitution
500 kcmil253.4415.411000 kcmil506.7Resistance-only comparison; not an ampacity or termination substitution
Use notes
  • Use this table for preliminary reference and arithmetic checks only.
  • Confirm equipment ratings, product markings, installation conditions, utility requirements, and the local authority requirements before design or field use.