Formula variables
- kW is the real load used for the correction estimate.
- Existing PF is the present power factor before correction.
- Target PF is the desired corrected power factor.
- V is the selected nominal system voltage for current comparison.
Assumptions
- The calculation uses real load in kW and the tangent difference between existing and target power factor angles.
- Current reduction is shown for the selected voltage and phase as a planning estimate.
- Capacitor staging, harmonics, switching transients, utility metering, and over-correction are not evaluated.
- Use utility bills, measurements, equipment data, and qualified engineering review before selecting correction equipment.
Examples
600 V commercial load. A 150 kW load improved from 0.78 PF to 0.95 PF requires about 71.04 kVAR and reduces estimated 600 V three-phase current by about 33.11 A.
Utility-bill workflow. Use measured demand and billing power factor when available. This worksheet gives the arithmetic target before equipment-specific review.