Formula variables
- Cable OD is the actual outside diameter in millimetres.
- Bend multiplier is the selected manufacturer or product-family value.
- Allowance percent is an optional extra layout margin.
- Radius is measured to the bend centreline unless manufacturer data states otherwise.
Assumptions
- Bend radius is calculated from cable outside diameter and the selected multiplier.
- The multiplier is a user-selected planning value; cable manufacturer instructions govern the actual bend limit.
- The optional allowance is added after the minimum radius calculation for layout conversation only.
- Cable construction, voltage class, armour, shielding, pulling setup, and field conditions can change the usable radius.
Examples
Armoured cable layout. A 28 mm OD cable with a 6x multiplier gives a 168 mm minimum radius and 336 mm bend diameter.
Manufacturer-data workflow. Replace the multiplier with the cable data sheet value when the actual construction or voltage class is known.